Table 6. Power supply
Description Value
U
aux
nominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz
110, 125, 220, 250 V DC
U
aux
variation 85...264 V AC
88...300 V DC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Maximum interruption time in the
auxiliary DC without resetting the RIO
modules
100 ms at Uaux nominal
Burden on auxiliary voltage supply at 240V AC
Module configuration Condition Consumption in VA
PSM_H + LECM + DIM8_H No DI activated 15.41
All DI activated at 90V DC 15.52
PSM_H + LECM + DOM No DO activated 15.52
All DO activated 16.23
PSM_H + LECM + DOM (5) All DO activated 23.00
PSM_H(2) + LECM + DOM(10) No DO activated 35.65
All 40 DO activated 43.24
Load sharing with other PSM in case
of two power supply used
Equal
Table 7. Binary inputs (Digital input module DIM8_H)
Description
Value
Operating range ±20% of the rated voltage
Rated voltage 110...250 V DC
Current drain 1.8...2.6 mA
Power consumption/input channel 200...750 mW
Threshold voltage 78 V DC
Reaction time 0.3 ms + 1 ms...4.0 s filtering time