*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHU¶V*XLGH
&KDSWHU ,QVWDOODWLRQ
32 3BSE 020 923R101
The ModuleBus Extension cable comes in three standard lengths:
TK801V003 - 300 mm (1 ft.)
TK801V006 - 600 mm (2 ft.)
TK801V012 - 1.2 meters (4 ft.).
ModuleBus length must not exceed 2.5 meters (8.2 feet) from FCI, TB815
Interconnection Unit, or ModuleBus Modem to the last MTU including extension
cables.
2SWLFDO0RGXOH%XV([SDQVLRQ
The FCI provides fiber optic expansion of the ModuleBus for up to 7 additional I/O
clusters or to drive equipment. The TB810/TB811 ModuleBus Optical Port must be
inserted in to the CI810 or CI830 FCI and TR815 Interconnect unit FCI to provide
optical ModuleBus expansion. See Figure 2-7 for location of the TB810/TB811on
)LJXUH  0RGXOH%XV ([WHQVLRQ &DEOH&RQQHFW LRQV
A
B
C
D
E
F
A
B
C
D
E
F
6
7
8
9
10
11
12
13
14
15
16
F
R
W
1
2
3
4
5
24V
DI810
C1234567C8
B1234567B8
A1234567A8
L1+ L2+
L2-L1-
L2+L1+
A
B
C
D
E
F
A
B
C
D
E
F
6
7
8
9
10
11
12
13
14
15
16
F
R
W
1
2
3
4
5
24V
DI810
C1234567C8
B1234567B8
A1234567A8
L1+ L2+
L2-L1-
L2+L1+
TB805
TB806
TK801V003
(300 mm)
Latch Release
Male Cable
Connector
Female Cable
Connector
(1 ft.)