*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHU¶V*XLGH
6HFWLRQ &DEOH5RXWLQJLQ(QFORVXUHV
3BSE 020 923R101 51
*URXQGLQJRI$GGLWLRQDO(TXLSPHQW
Additional power supply units of different types used by loads or sensor, and
modems and so on, and are located in the controller or I/O cabinet, shall be treated
in the following way with respect to grounding:
• The apparatus chassis (PE terminal) shall be connected to the installation
protective earth terminal or directly to cabinet chassis if the apparatus chassis
and bounding are accepted for protective bounding.
• No circuitry of an equipment shall be completely electrically floating but
referenced to a suitable potential.
&DEOH5R XWLQJLQ(QFOR VXUHV
There are some restrictions in mixing cables within a cabinet due to the risk of
interference.To describe the simple rules applicable at site installation, cables are
divided in categories. See Table 2-2 and the following rules for custom cabinet
installations:
• Within a category cables can be arbitrary mixed.
• The distance between cables belonging to different categories shall be kept >
50 mm (2").
• “Cabinet internal” junctions have their own defined spaces for routing.
Distance to other cables should always be >
50 mm (2").
Do not ground the same circuit at different points in the plant.
7DEOH &DEO H&DW HJRULHVLQD&DELQHW
&DEOH$SSOLFDWLRQ &DWHJRU\
Power supply (a.c. / d.c.) 1
Process I/O, shielded and unshielded cables 2
Communication 2
ModuleBus extension to S800 I/O 3