*URXQGLQJRI$GGLWLRQDO(TXLSPHQW
Additional power supply units of different types used by loads or sensor, and
modems and so on, and are located in the controller or I/O cabinet, shall be treated
in the following way with respect to grounding:
The apparatus chassis (PE terminal) shall be connected to the installation
protective earth terminal or directly to cabinet chassis if the apparatus chassis
and bounding are accepted for protective bounding.
No circuitry of an equipment shall be completely electrically floating but
referenced to a suitable potential.
 &DEOH5R XWLQJLQ(QFOR VXUHV
There are some restrictions in mixing cables within a cabinet due to the risk of
interference.To describe the simple rules applicable at site installation, cables are
divided in categories. See Table 2-2 and the following rules for custom cabinet
installations:
Within a category cables can be arbitrary mixed.
The distance between cables belonging to different categories shall be kept >
50 mm (2").
Cabinet internal” junctions have their own defined spaces for routing.
Distance to other cables should always be >
50 mm (2").
Do not ground the same circuit at different points in the plant.
7DEOH  &DEO H&DW HJRULHVLQD&DELQHW
&DEOH$SSOLFDWLRQ &DWHJRU\
Power supply (a.c. / d.c.) 1
Process I/O, shielded and unshielded cables 2
Communication 2
ModuleBus extension to S800 I/O 3