EasyManua.ls Logo

ABB SPAD 330 C - Technical Data Summary; Differential Stage Parameters

ABB SPAD 330 C
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Differential relay module type designations
- differential relay module for phase L1 SPCD 3C21
- differential relay module for phase L2 SPCD 3C22
- differential relay module for phase L3 SPCD 3C23
Biased differential stage I
d
>
Basic starting value p, setting range 20…50 % of I
n
Starting ratio s, setting range 10...50 %
HV side CT transforming ratio I
1
/I
n
correction, setting range 0.5…1.0
LV side CT transforming ratio I
2
/I
n
correction, setting range 0.5...1.0
Restraint threshold of the second
harmonic, setting range 10…20 % x I
d
Operation accuracy ±5 % of set value
Operating time 20…50 ms
High-set stage I
d
>>
Starting current I
d
>>, setting range 20…30 x I
n
Operation accuracy ±5 % of maximum value of setting range
Operation time 10…20 ms
Technical data
C