13
Data Code Data Values
direction
Current setting of the correction S6 R 0.5…1.0
setting I
1
/I
n
of the current trans-
formers of the HV side
Current setting of the correction S7 R 0.5…1.0
setting I
2
/I
n
of the current trans-
formers of the LV side
Potentiometer setting of the S11 R 20…50 % I
n
basic setting p
Potentiometer setting of the S12 R 10…50 %
starting ratio s
Local setting of the blocking S13 R 10…20 % I
d
threshold I
hr
>
Local setting of the high-set S14 R 20…30 x I
n
I
d
>>-stage
Switch-selected checksum of S15 R 0…255
switchgroup SG1 (Vector group
matching, SG1/1...6, output
relay latching, SG1/7, and block-
ing mode, SG1/8, selection)
Potentiometer setting of the cor- S16 R 0.5…1.0
rection value I
1
/I
n
of the trans-
forming ratio of the HV side
current transformers
Potentiometer setting of the cor- S17 R 0.5…1.0
rection value I
2
/I
n
of the trans-
forming ratio of the LV side
current transformers
Remotely set percentage of the S21 R,W(P) 0…999 %
basic setting p
Remotely set percentage of the S22 R,W(P) 0…999 %
starting ratio s
Remotely set percentage of the S23 R,W(P) 0…999 %
blocking threshold setting
Remotely set percentage of the S24 R,W(P) 0…999 %
tripping level of the I
d
>>-stage
Remotely set checksum of the S25 R,W(P) 0…255
switchgroup SG1
Effectuated remote setting of the S31 R 20…50 % I
n
basic setting p
Effectuated remote setting of the S32 R 10…50 %
starting ratio s
B