14
Data Code Data Values
direction
Effectuated remote setting of S33 R 10…20 % I
d
the blocking threshold
Effectuated remote setting of S34 R 20…30 x I
n
the tripping level of the I
d
>>-
stage
Effectuated remotely set check- S35 R 0…255
sum of switchgroup SG1
Recorded data
Differential current at the V1 R 0…50 x I
n
moment of tripping
Bias current at the moment of V2 R 0…50 x I
n
tripping
Maximum bias current V3 R 0…50 x I
n
measured
Maximum 2nd harmonic current V4 R 0…33 x I
n
measured
Other data
Remote resetting of latched V101 W 1 = resetting
output relays
Remote resetting of latched V102 W 1 = resetting
output relays and memorized
data
Effectuation of remote V150 R,W 0 = local settings
settings S11…S15 effectuated
1 = remote settings
S31…S35 effectuated
Event mask word V155 R,W 0…15, see section
“Event codes”
Opening of the password for V160 W 1…999
the remote settings
Changing or closing of pass- V161 W(P) 1…990
word for the remote settings
Testing of the self-super- V165 W 1 = self-supervision output and
vision function the IRF indicator is switched on
after ca.10 s and ca. 30 s there-
after the self-supervision resets
Filter calibration V168 R,W(P)
(for factory use)