Fig. 10. Voltage regulators SPAU 341 C1 in parallel operation using the minimizing circulating
current principle. The operation mode of the regulators is automatically selected according to the
circuit breaker configuration. The communication between the regulators is achieved by using
SPA/LON gateways.
Table 3. Regulator mode compared to circuit breaker configuration
CB 1 CB 2 CB 3 Regulator 1 Regulator 2
open closed open manual manual
closed closed open automatic manual
open closed closed manual automatic
closed closed closed parallel parallel
open open closed manual automatic
closed open open automatic manual
closed open closed automatic automatic