EasyManua.ls Logo

ABB SPCJ 4D29 - Page 60

ABB SPCJ 4D29
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
Note!
The event codes E52-E54 are generated by the
data communication unit (SACO 100M, SRIO
500M, SRIO 1000M, etc.)
Code Event Weight factor Default value
of the factor
E9 Starting of stage I
0
>11
E10 Resetting of starting of stage I
0
>20
E11 Operation of stage I
0
>41
E12 Resetting of operation of stage I
0
>80
E13 Starting of I
0
>> stage 16 1
E14 Resetting of starting of stage I
0
>> 32 0
E15 Operation of stage I
0
>> 64 1
E16 Resetting of operation of stage I
0
>> 128 0
Default checksum for mask V156 85
E17 Output signal TS1 activated 1 0
E18 Output signal TS1 reset 2 0
E19 Output signal SS1 activated 4 0
E20 Output signal SS1 reset 8 0
E21 Output signal SS2 activated 16 0
E22 Output signal SS2 reset 32 0
E23 Output signal SS3 activated 64 0
E24 Output signal SS3 reset 128 0
E25 Output signal TS2 activated 256 1
E26 Output signal TS2 reset 512 1
Default checksum for mask V157 768
E50 Restarting * -
E51 Overflow of event register * -
E52 Temporary interruption in data communication * -
E53 No response from the module over the data
communication * -
E54 The module responds again over the data
communication * -
0 not included in the event reporting
1 included in the event reporting
* no code number
- cannot be programmed