9. Open the valve in the tube to the conservator!
10. Pump the earlier drained oil back into the diverter switch housing.
11. Close the oil valve and disconnect the pump.
12. The level in the oil conservator and the gas cushion are now restored.
CAUTION
Avoid to do the restoring in damp weather since moisture will get into the diverter switch
housing. If the restoring has to be done in such weather, the incoming air has to be dehy-
drated and the drained oil protected from water.
Open
TC_00171
Air release valve
3. Repairs and adjustment
Fig. 9.