5 - Installation
• Once the phase of mechanical installation of the METER is nished,
it is necessary to congure the METER in order to make it compatible
with the inverter. Set the parameters on the meter display as set out in
the table:
Parameter Settings
Address 1
Protocol MODBUS
Baud rate 19200
Parity EVEN
The settings are made by using the keypad and the display on the meter:
1. Press for two seconds
to access the setup menu of the meter.
2. Press repeatedly
until the display shows “Set”.
- Press
to conrm.
3. Press repeatedly until the display shows “RS-485”.
- Press to conrm.
4. Press repeatedly
until the display shows “Prot”.
- Press
to access.
- Press to enable the change in the value.
- Press repeatedly until the display shows “Modbus”.
- Press to conrm the change.
- Press for two seconds
to return to the RS485 menu.
5. Press repeatedly
until the display shows “Baud”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly
and select 19200.
- Press
to conrm the change.
- Press for two seconds to return to the RS485 menu.
6. Press repeatedly until the display shows “Address”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly
and select 1.
- Press
to conrm the change.
- Press for two seconds
to return to the RS485 menu.
7. Press repeatedly
until the display shows “Parity”.
- Press
to access.
- Press
to enable the change in the value.
- Press repeatedly
and select even.
- Press
to conrm the change.