- 124 -
000698AG
7 - Operation
Local I/O Manager
In the Local I/O Manager sub-menu it’s possible to enable the ma-
nagement of power ows in order to optimize self-consumption or
avoid feeding power to the grid (this features will work only on inverter
equipped with UNO-DM-COM KIT (-X models) or UNO-DM-PLUS-COM
ETHERNET KIT (-E models)).
This section of the menu allows you to set the activation status of a relay
(available either as contact normally open – N.O. - and as a normally
closed contact -N.C.) and to congure customised alarm conditions.
This contact can be used, for example, to: activate a siren or a visual alarm,
control the disconnect device of an external transformer, or control an ex-
ternal device. A little description of the alarm type (e.g. “alarm lamp”) is re-
quired.
Relay switching can be set in 9 different modes using the submenu Set
Alarm Type (For the “Alarm Conf.”, “Al. Conf. Latch”, “Al. Conf. Ext.”,
“GoGo Rel(Auto)” and “GoGo Rel(Slave)” it is possible to congure
customised alarm conditions through the submenu Alarm Cong and
GoGo Cong):
Alarm Production - display text “Alarm-Contact (Production)”
The relay is activated (status: switched) whenever the inverter connects
to the grid; as soon as the inverter is disconnected from the grid (for
whatever reason that caused disconnection), the relay is in its resting
position.
• Alarm with reset at the end of the alarm signalling process - dis-
play text “Alarm-Contact (alarm ALL - no-latch)”:
The relay is activated (status: switched) whenever an error (code Exxx)
or warnings related to grid parameters out of range (Warning – codes
W003, W004, W005, W006, W007) are present on the inverter. The
alarm returns to its resting position when the alarm signal ends, i.e. be-
fore the inverter checks the grid parameters after the alarm state. This
is because grid control state is not an alarm state but a state of normal
operation.
Alarms for which the relay is activated
E001 E002 E003 E004 E005 E006
E007 E009 E010 E011 E012 E013
E014 E015 E016 E017 E018 E019
E020 E021 E022 E023 E024 E025
E026 E027 E028 E029 E030 E031
E032 E033 E034 E035 E036 E037
E046 E050 E053 E054 E055 E056
E057 E058 E077 E078 E081 E084
E089 W003 W004 W005 W006 W007
In the presence of W003, W004, W005, W006, W007 signalling, the alarm contact switches
to then reset itself at the end of the alarm signal. This means that during the absence of grid
voltage (display message “Missing Grid”) the alarm contact remains in its resting position.
INVERTER RUN
ERROR OCCURENCY
ERROR MESSAGE
t=15s
GRID RECONNECTION
t=based on Country Standard
ERROR
STILL
PRESENT
Yes No
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Relay State: Idle
Relay State: Idle
Relay State: Switched
INVERTER RUN
- PRODUCTION -
GRID DISCONNECTION
- NO PRODUCTION -
GRID RECONNECTION
t=based on Country Standard
DISCONNECTION
CAUSE IS STILL
PRESENT
Yes No
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Relay State: Idle
Relay State: Idle
Relay State: Switched