18
5. System Specifications
Model ATS-120 ATS-130 ATS-216 ATS-232
Input
Input voltage
100/110/115/120/127
( +/- 5% / 10% / 15% / 20% )
200/208/220/230/240
( +/- 5% / 10% / 15% / 20% )
Input voltage range 75Vac~150Vac 150Vac~300Vac
Input frequency
50 / 60Hz
( +/- 5% / 10% / 15% / 20% )
Input current 20A 30A 16A 32A
Output
Output voltage 100/110/115/120/127 200/208/220/230/240
Output current 20A 30A 16A 32A
Protection
Input Breaker(option)
Electronic circuit
Communication
RS-232, USB, Dry contact
external slot for option card(SNMP, RS-485)
Transfer time(ms)
8~12ms (Typical) *
Efficiency 99%(with full linear load)
Display LCD+LED
Connection
Input NEMA 5-20 x 2 NEMA L5-30 x 2 IEC C20 x 2
Terminal Block 6P
output NEMA 5-20 x 8
NEMA L5-30R x 1
NEMA 5-20x 8
IEC C19 x 1
IEC C13 x 8
IEC C19 x 2
IEC C13 x 16
Physical
Dimension,
D X W X H (mm)
275x440x44 275x440x88 275x440x44 275x440x88
Net Weight (kgs) 4 6 4 6
Environment
Operating
temperature
-5~40C @ 0~90% RH(non-condensing)
Standards
compliance
Safety
UL 60950-1/ CAN/CSA C22.2 No. 60950-1 /
IEC 60950-1
EMC
FCC Part 15 / EN62310-2