Hydrogen discharge function(Optional)When hydrogen discharge cycle comes, air conditioner start
the hydrogen discharge fan, the control switch closes.
hydrogen discharging function
parameter
Default value
Setting range
Unit
cycle
24
[072]
h
discharging time
5
[010]
Min
Emergency ventilation function (Optional): When the temperature inside cabinet is higher than
Emergency ventilation starting temperature, emergency ventilation fans run; when the temperature inside
cabinet is lower than Emergency ventilation stopping temperature, emergency ventilation fans stop.
Emergency ventilation function
parameter
Default value
Setting range
Unit
starting temperature
45
[2850]
stopping temperature
42
[2550]
5 Display screen
5.1 Display interface
NO.
Icon
Function
Function explanation
1
Refrigerating
running
Indicate whether refrigerating runs or not
2
Heater running
Indicate whether heater runs or not
3
Fan running
Indicate whether fan runs or not