EasyManuals Logo

AccuEnergy EV390 User Manual

Default Icon
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
EV/DV300 Series Power Meter
Appendix
V:2.0 Revised October 2018
52
Accuracy
Parameters
Accuracy
Resolution
Voltage
0.5%
0.1%
Current
0.5%
0.02%
Power
1.0%
0.1%
Reactive Power
1.0%
0.1%
Apparent Power
1.0%
0.1%
Power Factor
1.0%
0.1%
Frequency
0.5%
0.01Hz
Energy
1.0%
0.1kWh
Reactive Energy
1.0%
0.1kvarh
Drift with temp.
< 100ppm/
Stability
0.1%0 /year
Relay output (RO)
Output form
Mechanical Contact
Contact Resistance
100m ohm@1A, Initial
Max break voltage
250Vac, 30Vdc
Max break current
5A
Max isolate voltage
4000Vac rms
Digital output (DO)
Output form
Photo-MOS, NO
Optical Isolation
4000Vac rms
Max Positive Voltage
40Vdc
Max Positive Current
30mA
Max Reverse Voltage
6Vdc

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AccuEnergy EV390 and is the answer not in the manual?

AccuEnergy EV390 Specifications

General IconGeneral
BrandAccuEnergy
ModelEV390
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals