DOCUMENT NUMBER: OPMM-001E-R0
Proprietary Information: This document is the property of ADVANCED CONTAINMENT SYSTEMS, Inc. It shall not be copied
or duplicated and shall not be submitted to outside parties without the company consent.
Page 3 of 8 8/21/2017
2. DIMENSIONS:
2.1 Length: 37.75
2.2 Width: 26.5”
2.3 Height: 31.25
2.4 Weight: 160 lb
2.5 Housing: 0.063 Aluminum
2.6 Air Flow (High): 1975 cfm
2.7 Air Flow (Low ): 1000 cfm
2.8 Motor: 1.75 HP, 2 Speed
2.9 Power Supply: 115 VAC, 60 Hz, 20 amp
3. OPERATION:
3.1 Electrical Requirements:
3.1.1 The FA2000EC requires a minimum of 115 VAC, 60 Hz, 20 amp, power supply for
normal operation.
3.1.2 The unit requires a heavy duty industrial grade 12-3 cord, in good condition,
and should not exceed 50 ft. in continuous length for proper operation. If more
than 50 ft is needed, please consult with your distributor. Reducing the
required cord size/ gauge or increasing the length of the cord will increase the
amperage and can damage the 15 amp power supply receptacle.
3.1.3
3.1.4 The unit needs to be grounded properly, including the ground pin on the plug. Keep
electrical cords away from water and do not use a damaged cord.
3.2 Unit Set-up:
3.2.1 The unit should be located away from doorways or other make-up air sources.
3.2.2 Place the end of the exhaust port through an opening in the plastic barrier or wall
covering, using duct tape to seal off any opening. Do not exhaust to uncontaminated
or occupied areas.
CAUTION
DO NOT OPERATE THE FA2000EC WITHOUT THE HEPA FITLER INSTALLED!
OPERATING WITHOUT THE HEPA FILTER INSTALLED OR USING NON-APPROVED
POWER CORDS MAY CAUSE DAMAGE TO THE ELECTRICAL SYSTEM OR
MECHANICAL COMPONENTS. FAILURE TO COMPLY WILL VOID ALL WARRANTIES.