EasyManuals Logo

Acson awm10f User Manual

Acson awm10f
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
13
2
nd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 35°C DB
Outdoor DB, °C
35
Indoor DB
°C
Indoor WB
°C
TC (kW) SC (kW)
20 15 2.506 1.363
23 15 x
3
y
3
24 15 2.506 1.931
Total capacity, TC
3
x
= 2.506kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
3
ykW931.1
1.363kWkW931.1
C23C24
C20C24
=
°
°
°°
3
y
= 1.7 89kW
(b) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 40°C DB
Outdoor DB, °C
40
Indoor DB
°C
Indoor WB
°C
TC (kW) SC (kW)
20 15 2.311 1.205
23 15 x
4
y
4
24 15 2.311 1.773
Total capacity, TC
4
x
= 2.311kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
4ykW773.1
1.205kWkW773.1
C23C24
C20C24
=
°
°
°°
4
y = 1.631kW
* This is due to 2 different conditions with same WB temperature will have the same level of enthalpy. For
more details, please refer to psychrometrics chart