44
AWM-J-2010 Performance Data
(b) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 40°C DB
Indoor DB˚C Indoor WB˚C
Outdoor DB, ˚C
40
TC (kW) SHC (kW) PI (kW)
........
........
16
25
10.50 10.37 4.37
17
...........................................
x
6
y
6
z
6
18 11.36 9.03 4.43
Total capacity, TC
Interpolation Method:
17º C – 16º C
=
x
6
– 10.50kW
19º C – 16º C 11.36kW – 10.50kW
x
6
= 10.79kW
Sensible capacity, SHC
Interpolation Method:
17º C – 16º C
=
y
6
– 10.37kW
19º C – 16º C 9.03kW – 10.37kW
y
5
= 10.05kW
Power Input, PI
Interpolation Method:
17º C – 16º C
=
z
6
– 4.37kW
19º C – 16º C 4.43kW – 4.37kW
z
6
= 4.39kW