7
INSTALLATION
MONTAGE
H (m) / Ø in. mm 6 8 10
L (m) L (m) L (m)
0,0 17 53 100
0,5 15 47 100
1,0 13 41 99
1,5 11 34 84
2,0 9 28 68
2,5 7 22 53
3,0 5 15 37
3,5 3 9 22
Injector / Düse 2,5 kg/h 5,0 kg/h 10,0 kg/h
H (m) / Ø in. mm 464668
L (m) L (m) L (m)
4,0 51 100 26 100 65 100
2,5 45 100 22 100 57 100
3,0 38 100 19 97 49 100
2,5 32 100 16 81 40 100
2,0 26 100 13 65 32 100
1,5 19 97 10 49 24 77
1,0 13 65 6 32 16 51
0,5 6 32 3 16 8 26
Injector / Düse 2,5 kg/h 5,0 kg/h 10,0 kg/h
Type CA 100 CA 150 CA 200 Typ
Minimum fresch air requirement m
3
/h 95 133 224 Minimale Luftzufuhr m
3
/h
High level ventilation dm
2
2 2 2 Belüftung dm
2
Low level ventilation dm
2
5,7 8 13 Entlüftung dm
2
Draught stabiliser mm. 200 200 200 Zugregler mm.
Ø of chimney : Ø des Kaminanschlusses :
Height 5 m. mm. 180 210 270 Höhe 5 m. mm.
Height 10 m. mm. 150 180 230 Höhe 10 m. mm.
Height 15 m. mm. 140 160 210 Höhe 15 m. mm.
Height 20 m. mm. 130 150 200 Höhe 20 m. mm.
H
Oil connection
H
Ölversorgung
A Hight level ventilation
B Low level ventilation
C Draught stabiliser
D Cleanout cover
H Chimney height
I Diameter of chimney
J Internal fl ue connection
A Belüftung
B Entlüftung
C Zugregler
D Schauloch
H Kaminhöhe
I Kamindurchmesser
J Anschlußstück
Boiler House
This must conform to local regulations in particular in terms of
high and low level ventilation, size, fi re resistance etc. Gas fi red
installations must comply with the Gas Safety (Installation and
Use) 1984 Regulations as amended.
Heizungsraum
Der Heizungsraum muß den jeweiligen lokalen Vorschriften
in puncto Abmessungen, Hitzebeständigkeite der Wände,
Stahltüren, Kamine sowie Be- und Entlüftung entsprechen.