ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
2-128
© 2000, ADC Telecommunications, Inc.
DLP-539
Page 1 of 1
ACO (ALARM CUT-OFF) COMMAND
Summary:
This procedure provides instructions for silencing currently active audible alarms.
Any new alarms will cause the audible alarm relay to be activated again and the ACO state
canceled.
1. Use the arrow keys to select System Maintenance from the Main Menu. Press Enter or
Return.
2. Use the arrow keys to select Execute ACO (Alarm Cut-Off) from the System Maintenance
Menu.
3. Press Enter or Return to activate the ACO.
4. The following message appears across the screen and is shown in Figure 539-1.
Stop! You have completed this procedure.
6157-A
SYSTEM MAINTENANCE
1. Force/APS Commands
2. Reset/LED Test Commands
3. Execute ACO (Alarm Cut-Off)
4. Loopback Status/Commands
5. Di
6. Di ACO Executed
7. Up Press Any Key To Continue
8. Te
Press CONTROL-A For Assistance
Figure 539-1. ACO Executed Message
ACO Executed
Press any key to continue