EasyManua.ls Logo

ADF Web HD67507-A1 - Operation Mode; Modbus Master

ADF Web HD67507-A1
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual
Modbus TCP Slave
/
Modbus Master
Document code: MN67507_ENG Revision 2.400 Page 28 of 45
Figure 3c: “Set Communication
Operation Mode”
window
Figure 3d: “Set Communication
Modbus Master”
window
O
PERATION
M
ODE
:
In the section “Operation Mode” it is possible to define the working mode of the
converter (see page 33 for more info):
Routing Mode;
NAT Mode.
M
ODBUS
M
ASTER
:
This section is used to define the main parameters of Modbus line. The means of the
fields are:
In the field “Serial” the serial port to use is defined;
In the field “Baudratethe baudrate for the serial line is defined;
In the field “Parity” the parity of the serial line is defined;
In the field “Stop Bitsthe number of Stop Bits of the serial line is defined;
In the field “TimeOut (ms)” the maximum time that the converter attends
for the answer from the Slave interrogated is defined;
In the field Communication Idel Time (ms) the delay (idle time)
between two Modbus requests is defined;
In the field “Time Between Bytes (ms)” a custom delay between the bytes
is defined;
If the field Modbus Filteris checked, the filter for the not Modbus frames
is defined;