T QUASAR Flare Monitors Operation Manual Introduction 15
Note: Secure power input lines together after connection to the
Terminal block to prevent an accidental hazardous live condition in the
unlikely event that a terminal screw becomes loose. Sleeve or tie
wrapping is acceptable.
b. Connect the instrument loops and alarm outputs:
i. Connect the lines as needed for Normal Open (N.O.) or Normal Closed
(N.C.) relay to the corresponding locations on TB2.
ii. Connect the mA lines to the corresponding (MA-) and (MA+) outputs on
TB2. Cable shield, if present, is NOT recommended to be connected to
the instrument.
5. Proceed to the following chapters to complete the start-up checklist:
a. Chapter 5: Pilot Monitor (PM)
b. Chapter 6: Flare Monitor (FM)
c. Chapter 7: Smoke Monitor (SM)