B. Boiler
Standard boiler electrodes have a MNPT stainless steel bushing and are supplied with a FNPT cross


& hold). For a successful installation, it is critical to observe the recommended distances and pipe sizes
provided in the installation drawings.

󰀨

the electrode is exposed to water and not steam. Properly installed and adjusted, this device will prevent

NOTES:
1. Install a fully-ported type of valve between the electrode and the boiler. This allows
the electrode to be isolated for removal and cleaning.
 

 
best performance.
WARNINGS:
1. The probe must be fully immersed in the system water to read correctly.

2. Do not exceed a maximum water temperature of 436°F (224°C)
3. Do not exceed a maximum pressure of 350 psi (24.1 bar)
4. A throttling device must be installed downstream from the electrode.
Boiler Conductivity Electrodes
BE-4RTD and BE-32
Wiring Note: BE-4RTD probes require a 6-conductor cable from controller to probe; BE-32 probes only
require a 2 conductor cable.