b. FLASHING RED: indicates the component is
currently at an unacceptable run condition.
c. SOLID RED: indicates the component had once
been at an unacceptable run condition but is now
at an acceptable run condition. A ‘solid red’ light
can be cleared to a ‘solid green’ light by pressing
the START key.
2. PROBE: indicates the status of the ‘to process’ and ‘from
process’ sensor probes.
3. PUMP O/L: indicates the status of the pump motor
overload relay. See section 3.2 paragraph C 2 for more
proper operation of the pump overload relay.
4. HI PRESSURE: indicates the status of the refrigerant high
pressure safety switch.
5. LO PRESSURE: indicates the status of the refrigerant low
pressure safety switch.
6. LOW OIL: indicates the status of the low oil pressure safety
switch. This light activates on models with a 15 - 30 ton
semi-hermetic compressor.
7. COMPRESSOR: indicates the operating status of the
compressor.
8. FREEZESTAT: indicates the status of the freezestat safety
switch.
9. PHASE: indicates the status of the electrical phasing of the
unit. See section 3.2 paragraph B for more information on
correct unit phasing
H. COMMUNICATIONS DISPLAY
(figure 3.3I)
1. The communication display indicates the kind of exchange
between the host computer and the unit. A single light is
used:
Figure 3.3I