MK Series Portable Chiller : Air-Cooled : HE INSTRUMENT
Page: 56
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
D. Definition of the DIP switches are as follows:
SW1 - code page for EPROM:
ON - (default) code page 0 is active.
OFF - code page 1 is active.
SW2 - Setpoint range:
ON - (default) setpoint range is 70° to 48° F.
OFF - setpoint range is 90° to 10° F.
SW3 - Extended configuration:
ON - (default) extended configuration is DISABLED, the
display will not show additional information.
OFF - extended configuration is ENABLED, the display will
show the following after “CAP”:
ALT - alternate flow selection.
ton - chiller size in TONs.
Prb - from process probe calibration.
LPt - low pressure alarm delay.
SW4 - Cylinder count select, valid ONLY when SW5 is OFF:
ON - (default) 2 stages of unloading
OFF - 1 stage of unloading
SW5 - Chiller Type:
ON - (default) standard, no cylinder unloading.
OFF - cylinder unloading enabled, see SW4.