Chapter 4 Command Set 4-139
4021
Chapter 4
$AA6
Name Last Value Readback
Description The addressed analog output module is instructed to return the
latest output value it received from an Analog Data Out
command. If the module hasnt received an Analog Data Out
command since startup, it
will return its Start-up Output value.
Syntax $AA6(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog output module whose
value you want to
return.
6 is the Last Value Readback command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(data)(cr) if the command was valid.
?AA(cr) if an invalid command was issued.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
!
delimiter character indicating a valid command was received.
?
delimiter character indicating the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog output module.
(data) is the value that is returned by the analog output module.
The format of the data depends on the modules configured
data format.
(cr) is the terminating character, carriage return (0Dh).
Example command: $0A6(cr)
response: !0A03.000(cr)
The command tells the analog output module at address 0Ah to
return the last output value it received from an Analog Out
command.
The analog output module returns the value 3.000 mA.