Name Read Maximum Value
Description Read the Maximum values from all channels in a specified analog input
module
Syntax $aaMH(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal Modbus address
of the ADAM-6000 module to be read. (Always 01)
MH represents the read maximum value command.
(cr) is the terminating character, carriage return (0Dh)
Response >(data)…(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or communication
error or if the specified address does not exist.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal Modbus address of
an ADAM-6000 module.
(cr) is the terminating character, carriage return (0Dh)
Example command: $01MH(cr)
response:
>+10.000+10.000+10.000+10.000+10.000+10.000+10.000+10.000+10.000
Note: The latest data returned is the Average value of the preset channels in this module.
#aaMHn