Name Read Alarm Connection
Description Returns the High/Low alarm limit output connection of a specified input channel in the
addressed ADAM-6000 module
Syntax $aaCjRhC(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal Modbus address of an
ADAM-6000 module. (Always 01)
Cj identifies the desired analog input channel j (j : 0 to 7).
RhC is the Read Alarm Connection command.
h indicates alarm type (H = High alarm, L = Low alarm)
(cr) represents terminating character, carriage return (0Dh)
Response !aaCn(cr) if the command was valid
?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or communication error
or if the specified address does not exist.
! delimiter character indicating a valid command was received.
aa represents the 2-character hexadecimal Modbus network address of the corresponding
ADAM-6000 module.
Cn identifies the desired digital output channel n (n : 0 to 1) whether interlock with the
alarm of the specific analog input channel. If the values of n are ‘*’, the analog input has no
connection with a digital output point.
(cr) represents terminating character, carriage return (0Dh)
Example command: $01C1RLC(cr)
response: !01C0(cr)
Channel 1 of the ADAM-6000 module at address 01h is instructed to read its Low alarm
output connection.
The system responds that the Low alarm output connects to the digital output at channel 0
in the specific ADAM-6000 module.