EN
Table of countries
Note
After being switched on for the first time the inverter operates using default values until a country has been selected.
Country Grid voltage Grid frequency
Recon-
nection
time
Default values ±10 % of the rated voltage (0.10 s) –0.3 Hz / +0.2 Hz of the rated frequency (0.10 s) 180 s
Greece (Mainland) –20 % / +15 % of the rated voltage (0.50 s) ± 0.5 Hz of the rated frequency (0.50 s) 180 s
Greece (Islands) –20 % / +15 % of the rated voltage (0.50 s) –2.5 Hz / +1.0 Hz of the rated frequency (0.50 s) 180 s
Netherlands –20 % / +10 % of the rated voltage (2.00 s) –2.0 Hz / +1.0 Hz of the rated frequency (2.00 s) 30 s
Belgium
1)
–15 % / +10 % of the rated voltage (0.12 s) –2.5 Hz / +0.5 Hz of the rated frequency (0.12 s) 30 s
Belgium unlimited
2)
–15 % / +10 % of the rated voltage (0.12 s) –2.5 Hz / +0.5 Hz of the rated frequency (0.12 s) 30 s
France ±15 % of the rated voltage (0.20 s) ± 0.5 Hz of the rated frequency (0.20 s) 30 s
Spain –15 % / +10 % of the rated voltage (0.20 s) ± 1.0 Hz of the rated frequency (0.20 s) 180 s
Portugal ±15 % of the rated voltage (0.20 s) –3.0 Hz / +1.0 Hz of the rated frequency (0.50 s) 20 s
Ireland ±10 % of the rated voltage (0.50 s) –2.0 Hz / +0.5 Hz of the rated frequency (0.50 s) 30 s
Slovenia ±15 % of the rated voltage (0.20 s) –3.0 Hz / +1.0 Hz of the rated frequency (0.20 s) 30 s
Italy 1 ±20 % of the rated voltage (0.10 s) ± 0.3 Hz of the rated frequency (0.10 s) 30 s
Italy 2 ±20 % of the rated voltage (0.10 s) ± 1.0 Hz of the rated frequency (0.10 s) 30 s
Czech Republic ±15 % of the rated voltage (0.20 s) ± 0.5 Hz of the rated frequency (0.20 s) 30 s
Austria –20 % / +15 % of the rated voltage (0.20 s) –3.0 Hz / +1.0 Hz of the rated frequency (0.20 s) 30 s
Great Britain –10 % / +15 % of the rated voltage (1.50 s) –3.0 Hz / +0.5 Hz of the rated frequency (0.50 s) 180 s
Sweden ±15 % of the rated voltage (0.20 s) –3.0 Hz / +1.0 Hz of the rated frequency (0.50 s) 30 s
Germany / Switzerland –20 % / +15 % of the rated voltage (0.20 s) –2.5 Hz / +0.2 Hz of the rated frequency (0.20 s) 30 s
Australia –13 % / +17 % of the rated voltage (2.00 s) –3.5 Hz / +5.0 Hz of the rated frequency (2.00 s) 60 s
Turkey –20 % / +15 % of the rated voltage (0.20 s) –2.5 Hz / +0.2 Hz of the rated frequency (0.20 s) 30 s
Israel –13 % / +17 % of the rated voltage (2.00 s) –3.5 Hz / +5.0 Hz of the rated frequency (2.00 s) 300 s
1)
maximum output power of 10,000 W (StecaGrid 10000 3ph only)
2)
maximum output power of 10,300 W (StecaGrid 10000 3ph only)
51
737.096 | 11.37