How to address 'Airflow Fault During Ignition' in an Aerco Water Heater?
- BBenjamin ThompsonDec 1, 2025
To address an 'AIRFLOW FAULT DURING IGNITION' in your Aerco Water Heater, you can try the following: * Check the combustion blower for signs of excessive heat or high current drain that may trip thermal or current overload devices. * Inspect the inlet to the combustion blower including any ductwork leading up to the combustion blower for signs of blockage. * Remove the Blower proof switch and inspect for signs of blockage, clean or replace as necessary. * Remove the blocked-air inlet switch and inspect for signs of blockage, clean or replace as necessary. * Measure the Blower proof switch for continuity with the combustion blower running. If there is an erratic resistance reading or the resistance reading is greater than zero ohms, replace the switch. * Measure the blocked-air...