17
English
TECHNICAL DATA
Performances refer to following conditions:
Sound pressure measured at 5 mt.s in free field
conditions Q = 2.
Cooling:
- room temperature 27 °C d.b., 19 °C w.b.;
- water temperature input 16 °C;
- Pre-setted condensing water valve (19 bar).
Power supply : 230 V - 1 - 50 Hz (CWX T: 400 V - 3+N - 50 Hz)
* EXWP 180 - 240
R407C
[W] 3400 5100 5100 6550 6550
[W] 3500 - - - -
[W] - 5150 5150 6600 6600
[W] 1225 1870 1820 2470 2370
[W] 1225 - - - -
- 1870 1820 2470 2370
[A] 5,9 9,2 3,7 12,4 4,6
[A] 5,9 - - - -
[A] - 9,2 3,6 12,4 4,6
[l/h] 160 230 230 330 330
[l/h] 160
[l/h] - 230 230 330 330
Rollkolben
[A] 33,5 47 23 64 27
[dB(A)] 29 35 35 36 36
[g] 480 800 800 1000 1000
[mm] 450 450 450 570 570
[mm] 470 470 470 470 470
[mm] 260 260 260 260 260
[kg] 31 40 40 48,5 48,5
SOUND DATA
Sound pressure* Sound power band middle frequency (Hz) global
Mod.
125 250 500 1000 2000 4000 8000
dB(A) dB dB dB dB dB dB dB dB (A)
CWX 1217 35,2 63,0 52,5 59,4 43,8 38,8 33,2 27,5 57,2
CWX 1817 37,3 63,5 60,1 60,3 49,7 44,5 37,6 32,7 59,3
CWX 2417 40,0 72,0 62,0 61,1 49,5 53,1 39,0 33,3 62,0
* = Open space, front distance from the unit 5 m, direction factor = 2
WATER COUPLINGS
REFRIGERANT RECHARGE
Mod. CWX 1217 1817 2417
Refrigerant recharge 20 [g/m] 20 [g/m] 20 [g/m]
For line lenght longer than 10 - 15 [m] 10 - 15 [m] 10 -15 [m]
Mod. CWX 1217 1817 2417
Diameter 1/2” 3/4” 3/4”
R407C
CWX 1217 1817 1817 T 2417 2417 T
EXWP* - EX-M - EXC
Cooling capacity EWAH
EWPH
EXWP* - EX-M - EXC
Total input power EWAH
EWPH
EXWP* - EX-M - EXC
Total input current EWAH
EWPH
EXWP* - EX-M - EXC
Water consumption at 16 °C EWAH
EWPH
Compressor type
Peak current
Sound pressure
Refrigerant gas charge R407C
Altezza
Dimensions Larghezza
Profondità
Net weight R407C