Heat recovery units with refrigeration circuit - URX_CF -
30
Selection and installation manual
GB
10. The compressor does not start due Pressure switch out of order Check and replace
to the intervention of the Machine completely empty See point 11)
low pressure switch Poor air flow Check the air duct and the state of
the filters.
Blocked refrigerant filter Check and replace
•The thermal expansion valve does not • Check, clean or if necessary
function correctly replace it.
11. Lack of gas Leak in the refrigerating circuit • Check the refrigerating circuit
with a leak detector
12. Hot liquid pipe Lack of refrigerant • See point 11)
13. The refrigerating circuit functions Lack of refrigerant See point 11)
correctly but with insufficient Presence of humidity or incondensable • Replace the filter and if necessary
proficiency in the refrigerating circuit drain and refill the circuit
14. Compressor suction tube Thermal expansion valve • Check the valve and
frosted if it is not working
correctly replace it
Poor air flow • Check filters, fans and ducts.
Lack of refrigerant • See point 11)
Blocked liquid filter • Clean or replace
15. Abnormal noise in the system Vibrations in the pipes • Secure the pipes
Noisy compressor • Check electrical phases connection
Noisy thermostatic valve • Check and add refrigerant
16. Evaporator coil Lack of refrigerant in the circuit: • Check for leaks and eliminate them
before bubbles visible in the indicator.
topping up with refrigerant
.
Thermostatic expansion valve over . Reduce the overheating of the
closed: suction pipe too hot thermostatic expansion valve
turn the valve stem and
check the suction pressure
.
Thermostatic expansion valve over .
Change the valve or free the
closed: expansion valve bulb control pipe.
partially blocked or pressure intake pipe
blocked
Filter-drier blocked: bubbles in the • Change the filter-drier.
flow indicator and liquid pipe colder
at the filter drier outlet
The manifold feed pipes are Remove the obstruction; clean or change
blocked or oil has accumulated in the the evaporator.
coil: not all of the evaporator circuits
are working
17. Compressor too hot •Thermostatic expansion valve • Reduce the overheating of the
over closed: excessive overheating thermostatic valve
of the evaporator discharge gas
18. Compressor to cold and noisy Expansion valve over open: Measure and reset the overheating
the system works with the overheating by closing the valve
to low (return of liquid to the compressor).
Thermostatic valve out of order: the stem or Replace the valve or free the
the seat of the expansion valve is pressure inlet pipe
corroded. Pressure inlet pipe blocked.
Foreign objects between the stem and the seat
Clean the stem and the holes of the
of the thermostatic valve: abnormal function thermostatic valve
of the thermostatic valve