Heat recovery units with refrigeration circuit - URX_CF -
29
Selection and installation manual
GB
Diagnosis and trouble-shooting
1. Insufficient air flow rate • Fans rotation speed • Clean the components
too low
increase the fan speed
• Pressure drop of the
distribution system underestimated
• Blocked filters
• Blocked intake grating
• Coil incrustation
2. Excessive air flow rate • Fans rotation speed • reduce the fan speed
too high
• Pressure drop of the
distribution system overestimated
• Filters not fitted • Fit filters
3. No air flow rate
• Power supply off
Make sure power supply is available
• Electric motor burnt out • Replace the electric motor
4. Abnormal noise Excessive flow rate • Reduce flow rate
• Bearings worn or defective Replace bearings
• Foreign objects on the fan blades • Clean blades
5. Water movement Trap Blocked • Clean trap
No trap or incorrectly carried out Use an adequate trap
6. The compressor does not start Defective connection or contacts open
Check the voltage and close the contact
Thermostat does not • System at temperature, no
respond request; check the setting and the
functioning
• Safety device does not • See point 9) and 10)
respond
Defective compressor • Replace compressor
7. The compressor does not start Compressor burnt out or seized • Replace compressor
Compressor remote control switch de-energised
• Check the voltage across
the operating time of the protection;
automatic compressor shutdown
Power circuit open Check why the protection cut in
compressor; automatic shutdown
8. The compressor starts and then stops • Defective compressor remote control switch Check and if necessary replace it
Defective compressor
Check and if necessary replace it
9. The compressor does not start due to •Pressure switch out or order Check and replace
the intervention of the high pressure • Excessive refrigerant • Discharge excess gas
switch
Presence of incondensable gas • Refill the circuit after having
in the refrigerating circuit discharged and placed in vacuum.
The condensate coil is not sufficiently
• See point 1)
covered in air
Blocked refrigerant filter Check and replace