MANUALE D’INSTALLAZIONE
INSTALLATION MANUAL
MANUEL D'INSTALLATION
INSTALLATIONSANLEITUNG
MANUAL DE INSTALACIÓN
VCZ 41 - 42 - 43
VCZ 4124 - 4224 - 4324
KIT VALVOLA A 3 VIE
per ventilconvettori
FCZ
THREE WAY KIT VALVES
for fan coils
FCZ series
VANNE À TROIS VOIES VCZ
pour ventiloconvecteurs
série FCZ
KIT 3-WEG-VENTIL
für Gebläsekonvektoren
Baureihe FCZ
VÁLVULA MOTORIZADA CON 3 VÍAS VCZ
para fan coils
serie FCZ
AVCZUJ 1906 - 4413930_02
Question and Answer IconNeed help?

Do you have a question about the AERMEC VCZ41 and is the answer not in the manual?

Overview

This document describes the VCZ series of three-way kit valves from AERMEC, designed for use with FCZ, FCX, FCS, FHX, and VEC series fan coils. The manual provides installation instructions and technical specifications in multiple languages, including English, Italian, French, German, and Spanish.

Function Description

The VCZ three-way kit valve is an "all or nothing" type valve, meaning it is either fully open or fully closed, and is normally closed. It is designed to regulate water flow in fan coil units, enabling control over heating or cooling. The kit includes the valve, an actuator, and the necessary hydraulic fittings. These valves can be installed on fan coils with either right or left connections. The valve's operation is controlled by specific control panels that support valve management.

Important Technical Specifications

The VCZ series includes models VCZ 41, 42, 43, 4124, 4224, and 4324.

  • Electrical Supply:
    • VCZ 41-42-43: 230V (±10%) 50Hz
    • VCZ 4124-4224-4324: 24V ~ 50Hz
  • Initial Input Power:
    • VCZ 41-42-43: 46VA
    • VCZ 4124-4224-4324: 6VA
  • Input Power During Operation: 2.5W for all models.
  • Water Temperature Range: 4°C ÷ 80°C.
  • Usable Liquids: Water (with glycol ≤ 50%).
  • Operating Time: 2 minutes to 4 minutes.
  • Maximum Differential Pressure: 30kPa.
  • Maximum Working Pressure Applied to Fan Coils: 800kPa.
  • Environmental Operating Conditions:
    • Temperature: 0°C ÷ 40°C
    • Relative Humidity: 10% ÷ 90% (without condensation)
  • Environmental Storage Conditions:
    • Temperature: -18°C ÷ 60°C
    • Relative Humidity: 10% ÷ 90% (without condensation)
  • Actuator Water Protection Level: IP44 in compliance with EN 60529.
  • Actuator Electrical Protection Level: Class II.
  • Valve Connections: 3/4" for main connections (A-AB-B) and 1/2" for by-pass (AB-B).
  • Pressure Drop (Kvs):
    • Kvs AB-A: 2.5
    • Kvs AB-B (by-pass): 1.6

The flow direction in the valve is critical for proper operation. When the valve is powered, the flow is from A to AB. When the valve is not powered, the flow is from B to AB.

Usage Features

The VCZ kit valves are designed for straightforward integration into existing fan coil systems. They are compatible with a wide range of AERMEC fan coil units, including FCZ, FCX, FCS, FHX, and VEC series. The kit includes an insulating shell for the valve body, which is essential for preventing condensation, especially in cold water circuits, thus avoiding water spillage into the environment.

Installation requires careful attention to the flow direction, indicated by an embossed symbol on the valve body. The valve body must be installed without excessive torsion. The kit also includes a minimum temperature probe (SW) that needs to be detached from the coil and fastened to the upstream delivery pipe of the valve using a specific probe holder. This probe helps monitor the system's temperature.

Electrical connections are made to the unit's control board, following the wiring diagrams provided in the fan coil or control panel manuals. Hydraulic connections are made directly to the valve using 1/4" flat sealing gaskets on the plant side, and O-ring seals manage connections between the valve kit and the fan coil coil.

Maintenance Features

Maintenance primarily involves ensuring proper installation and periodic checks. The manual emphasizes that electrical wiring, fan coil installation, and accessory setup must only be performed by qualified technical professionals. Key checks include measuring the electrical system's insulation strength and testing the continuity of protection wires.

During any intervention, it is crucial to disconnect the power supply and use appropriate individual protection devices to prevent electric shock. If the valve needs to be disassembled, the gaskets must be replaced with new ones of the same characteristics to ensure proper sealing. All tubes, valves, and fittings must be completely insulated, and any exposed tubes or joints should be re-insulated to maintain efficiency and prevent condensation. Regular inspection of the insulation can help identify and address any degradation over time.