54
IVEDPY 1110 - 4879010_01
VMF-E1
VMF-SIT
VED
VMF-E1
VMF-SIT
VED
VMF-E1
VMF-SIT
VED
VMF-E5B
VMF-E5N
VMF-E4VMF-E4VMF-E4
WARNING: the VMF-E5 panel allows the management of
the individual masters.
The slave units connected to each master cannot be individually
managed from the VMF-E5 panel, but they acquire the settings
of the master to which they are connected.
• Maximum number of MASTER fancoils = 64
• Maximum number of SLAVE fancoils that can be connected to each MASTER = 5
VMF-E5B / VMF-E5N SYSTEM'S MAIN SUPERVISION INTERFACE
Built-in panel available in two colours,
VMF-E5B white and VMF-E5N black
with graphic LCD backlit display and
capacitive keyboard, allows the cen-
tralised control/command of a com-
plete hydronic system consisting of:
Fan coils: up to 64 fan coil zones com-
prising 1 master + maximum 5 slaves.
Chiller/heat pump equipped with con-
trols Modu_Control, GR3 and pCO2 /
PCO ³ (required accessory RS 485 inter
-
face respectively MODU-485A, AER485,
AER485P2 / AER485P1)
Circulators: maximum of 12 configu-
rable zone circulators.
Boiler: boiler consensus management
for hot water production.
• Heat recovery units: consents up to 3
per programmable recovery units based
on the timing and/or by measuring the
air quality obtained with the VMF-VOC
accessory.
Domestic hot water module: complete
management of the domestic hot water
production through the control of:
- Diverting valve/circulator
- Supplementary heater
- Accumulation temperature probe
- Anti-legionella circuit
The main feature is the possibility of man-
aging the plant through dedicated algo-
rithms to achieve a comfortable envi-
ronment with energy saving in mind.
See the accessories manual for complete
information on its features.
CAUTION! : Not all accessory features are applicable to the unit. Check the compatibility of the functions with the
configuration of the unit and other accessories used. For complete information concerning the functions, refer to the technical
manuals of the unit and the accessories.