On-Grid PV Inverter

Questions and Answers

  • S
    santanaannaSep 23, 2025
    What does IsolationErr mean on my Afore BNT020KTL Inverter?
    • C
      christina24Sep 23, 2025
      If your Afore Inverter displays IsolationErr, it indicates low insulation resistance. Check the resistance between PV(+) and ground, and PV(-) and ground, ensuring it's greater than 2MΩ.
  • D
    Donna MoyerAug 23, 2025
    Why does my Afore Inverter show GridV.OutLim?
    • K
      Katherine WilliamsAug 23, 2025
      If your Afore Inverter displays GridV.OutLim, it means the grid is fluctuating or there's a voltage unbalance between phases. The inverter will automatically restart once the grid returns to normal. You can also check each phase's voltage via the inverter LCD.
  • K
    Kelli RussoAug 25, 2025
    What to do if my Afore BNT020KTL displays GridF.OutLim?
    • M
      Mrs. Rebecca RodriguezAug 26, 2025
      If your Afore Inverter displays GridF.OutLim, it indicates the grid is fluctuating or the grid frequency is outside the set range. Once the grid returns to normal, the inverter will restart automatically. Verify that the inverter frequency setting range is correct and ensure the AC output wiring is securely connected.
  • T
    Toni WilliamsAug 27, 2025
    What causes IntFaultE on my Afore Inverter?
    • M
      Megan JonesAug 27, 2025
      If your Afore Inverter shows IntFaultE, it indicates an over current fault. The inverter will automatically restart once the grid returns to normal.
  • C
    Chelsea PriceAug 27, 2025
    What does IntFaultD mean on my Afore BNT020KTL?
    • D
      Diana StevensAug 27, 2025
      If your Afore Inverter displays IntFaultD, it indicates a software over current fault. Check that the PV array configuration is correct. If there are fluctuations on the grid, wait for it to return to normal; the inverter will restart automatically.
  • S
    Seth ThompsonSep 17, 2025
    What does IntProtectR mean on my Afore BNT020KTL Inverter?
    • M
      Matthew DavisSep 17, 2025
      If your Afore Inverter displays IntProtectR, it indicates DCI circuit protection. Turn off the AC and then the DC circuit breaker, then restart the inverter. If the problem continues, replace the control board.
  • B
    Brian StephensSep 14, 2025
    What does IntProtectA mean on my Afore Inverter?
    • R
      Robert OsborneSep 14, 2025
      If your Afore Inverter displays IntProtectA, it indicates bias current protection. First, turn off the AC and DC circuit breakers, then restart the inverter. If the problem persists, consider replacing the control board.
  • E
    Elizabeth ScottSep 15, 2025
    How to resolve IntProtectC error on my Afore BNT020KTL?
    • N
      Noah ParkerSep 15, 2025
      If your Afore Inverter displays IntProtectC, it indicates inverter current protection. Turn off the AC and then the DC circuit breaker, restart the inverter, and check that each phase's AC voltage is correct via the LCD.
  • A
    Albert QuinnSep 6, 2025
    What should I do if my Afore BNT020KTL shows IntProtectG or IntProtectI?
    • K
      Kevin SalazarSep 6, 2025
      If your Afore Inverter displays IntProtectG or IntProtectI, it indicates a bus voltage protection issue. To resolve this: 1. Check the AC output wiring is well connected and uses stranded copper cable. 2. Verify the PV array configuration is correct. 3. Ensure the voltage difference between BUS+ and BUS- is not too high.
  • D
    douglastylerSep 3, 2025
    What causes IntProtectQ on my Afore Inverter?
    • T
      Tammy EvansSep 3, 2025
      If your Afore Inverter displays IntProtectQ, it indicates DCI protection. Check that the PV array configuration is correct. Also, verify that the voltage difference between BUS+ and BUS- is not too high.

Summary

Safety & Symbols

Installation

Installation Steps

Outlines the sequential process for installing the PV inverter.

Electrical Connection

PV Connection

Details the procedure and requirements for connecting PV strings.

Grid Connection

Describes how to connect the inverter to the AC grid.

Operation

Startup Setting

Guides through the initial configuration process after installation.

Parameter Setting

Details how to adjust and configure inverter operational parameters.

Commissioning

Commissioning Procedures

Lists steps to follow before and during system startup.

Shut Down & Restart

Maintenance & Troubleshooting

Fault Code and Troubleshooting List

Provides error codes and corrective actions.

Afore BNT020KTL Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200-1000 V
Number of MPPTs2
AC Voltage Range310 - 480 V
THDI< 3%
AC Grid Frequency50 / 60 Hz
Max. Efficiency98.6%
DC ConnectionMC4
Protection DegreeIP65
Weight32 kg
Nominal AC Power20000 W
Max. AC Power22000 W
Nominal AC Voltage400 V
Power Factor0.8 leading - 0.8 lagging
Operating Temperature Range-25°C to +60°C