5.2 Mounting the product
1. Mount the product vertically.
2. Before performing welding work, remove the welding sockets from the
probe.
3. Install the product in parallel with a vertical section of the flow line.
4. Install the product in the boiler circuit upstream of the mixer.
- The switch-off level of the product must be at least 100 mm above th
e
h
ighest heated surface of the heat generator.
5.3 Electrical connection
DANGER
ELECTRIC SHOCK
Verify that the degree of protection against electric shock (protection class,
double insulation) is not reduced by the type of electrical installation.
Verify that the cover is not exposed to water.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRIC SHOCK CAUSED BY LIVE PARTS
Disconnect the mains voltage supply before performing the work and ensur
e
th
at it cannot be switched on.
Verify that no hazards can be caused by electrically conductive objects or
media.
Failure to follow these instructions will result in death or serious injury.