VF Series | Non-Cycling | 10 - 2,000 scfm
DHT Series | High Inlet Temperature | 20 - 125 scfm
AES Series | Energy Saving Digital Scroll | 600 - 10,000 scfm
REFRIGERATED DRYER USER MANUAL
The information in this manual is current as of its publication date and applies to VF, DHT, and AES Series refrigerated air dryers until next revision of this manual.
Copyright © December 2017 Aircel, LLC. All rights reserved.
WARRANTY NOTICE
Failure to follow the instructions
and procedures in this manual, or
misuse of this equipment, will void its
warranty.
WARNING!
Users are required to read the entire
User Manual before handling or using
the product. Keep the User Manual in
a safe place for future reference.

Table of Contents

Other manuals for Aircel DHT-20

Questions and Answers

  • J
    Jim WardAug 9, 2025
    What to do if there is water downstream of my Aircel Dryer system?
    • K
      Kristie HammondAug 10, 2025
      If you notice water downstream of your Aircel Dryer system, several issues could be the cause. First, the timer drain or drain solenoid may have failed; in this case, replace the timer drain. Another potential cause is bulk liquid entering the dryer from upstream. Check the drains on the after cooler or air compressor. Also, verify that the inlet compressed air temperature and CFM flow rate meet the dryer system's specifications. A leak in the heat exchanger could also be responsible, requiring its replacement.
  • C
    Cassandra LamAug 15, 2025
    How to fix failed drain solenoid in Aircel DHT-20?
    • J
      Jacqueline MayAug 15, 2025
      If the drain solenoid in your Aircel Dryer has failed, replace the timer drain.
  • D
    Destiny MillsAug 20, 2025
    How to fix failed or short circuited timer on drain in Aircel Dryer?
    • E
      Eric GarciaAug 20, 2025
      If the timer on the drain of your Aircel Dryer has failed or short-circuited, replace the timer drain.
  • S
    Stacey JohnsonAug 25, 2025
    What to do if the refrigeration compressor is overheated in Aircel Dryer?
    • A
      Angela RuizAug 25, 2025
      If the refrigeration compressor in your Aircel Dryer is overheated, turn off the dryer and wait 20 to 40 minutes before restarting it.
  • A
    Ann ThomasAug 30, 2025
    What to do if my Aircel Dryer system is not working properly and there is water downstream?
    • L
      lucasnorrisAug 30, 2025
      If your Aircel Dryer system isn't working correctly and there's water downstream, several factors could be at play. The refrigeration compressor might be stopping because of a dirty condenser coil, leading to high pressure, so you should clean the condensing coil and make sure the unit has enough ventilation. Another reason could be the refrigeration compressor cycles on and off and can't keep suction pressure, in that case, inspect the condensing coil for any obstructions. If clear, use refrigerant pressure gauges to see if the unit is low on refrigerant. Also consider the possibility of low refrigerant levels, possibly due to a leak in the air-to-refrigerant side of the heat exchanger, so you should repair or replace the heat exchanger and recharge the system according to specifications.
  • S
    Steven RileySep 3, 2025
    Why is there water downstream of my Aircel Dryer system or no discharge from the separator/filter?
    • R
      Rebecca WagnerSep 4, 2025
      There are several reasons why you might find water downstream of your Aircel Dryer system or a lack of discharge from the separator/filter. It could be due to a failed or short-circuited timer on the drain or a failed drain solenoid, in which case you should replace the timer drain. Another cause may be bulk liquid entering the dryer from upstream, so check the drains on the aftercooler or air compressor. Also, verify that the inlet compressed air temperature and CFM flow rate to the dryer do not exceed the dryer's capacity; adjust as needed to meet specifications. A leak in the air-to-air heat exchanger can also cause this issue, requiring replacement of the heat exchanger.