7-1
ELECTRICAL DATA
Revision 0
7. ELECTRICAL DATA
7.1 Single and Three Phase Units
MODEL FLO 7 N LCD FLO 9 N LCD FLO 12 N LCD FLO 14 N LCD
Power Supply
To indoor To indoor To indoor To indoor
1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz
Max Current, (A) 4.3 6.0 8.2 9.5
Circuit Breaker,(A) 10 10 15 15
Power Supply Wiring.
(No. x Cross Section mm
2
)
3x1.5 mm
2
3x1.5 mm
2
3x1.5 mm
2
3x1.5 mm
2
Interconnecting Cable RC
Model
(No. x Cross Section mm
2
)
5 x 1.0 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
5 x 1.0 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
5 x 1.5 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
5 x 1.5 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
Interconnecting Cable ST Model
(No. x Cross Section mm
2
)
4x1.0 mm
2
4x1.0 mm
2
4x1.5 mm
2
4x1.5 mm
2
MODEL FLO 18 N LCD FLO 24 N LCD FLO 24 N LCD FLO 24 N LCD
Power Supply
To indoor To indoor(Option) To Outdoor To Outdoor
1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz 3PH-400V-50Hz
Max Current, (A) 11.1 14 14 3x6
Circuit Breaker,(A) 15 20 20 3x10
Power Supply Wiring.
(No. x Cross Section mm
2
)
3 x 1.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
5 x 1.5mm
2
Interconnecting Cable RC Model
(No. x Cross Section mm
2
)
5 x 1.5 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
5 x 2.5 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
6 x 2.5 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
6 x 2.5 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
Interconnecting Cable ST Model
(No. x Cross Section mm
2
)
4 x 1.5 mm
2
4x2.5 mm
2
+ 2x0.5 mm
2
5x2.5 mm
2
+ 2x0.5 mm
2
5 x 2.5 mm
2
+ 2 x 0.5mm
2
(OCT sensor)
MODEL FLO 30 N LCD FLO 30 N LCD
Power Supply
To Outdoor To Outdoor
1PH-230V-50Hz 3PH-400V-50Hz
Max Current, (A) 17 3x9.2
Circuit Breaker,(A) 25 16
Power Supply Wiring.
(No. x Cross Section mm
2
)
3 x 4mm
2
5 x 2.5mm
2
Interconnecting Cable RC Model
(No. x Cross Section mm
2
)
6x2.5 mm
2
+ 2x0.5 mm
2
(OCT sensor)
6 x 1.5 mm
2
+ 2 x 0.5 mm
2
(OCT sensor)
Interconnecting Cable ST Model 5 x 2.5 mm
2
+ 2 x 0.5 mm
2
5 x 1.5 mm
2
+ 2 x 0.5 mm
2
(No. x Cross Section mm
2
)
(OCT sensor) (OCT sensor)
NOTE
Power wiring cord should comply with local lows and electrical