12a-31
CONTROL SYSTEM
Revision 0
12A.14. Clogged Air filter
• Filter LED ON after 512 HR
• Filter LED is turned OFF, and the Filter Timer is restarted by pressing the reset
button.
12A.15. Ionizer
Ionizer output logic
Models: All
Operation mode: All
• ON condition:
IFAN turn ON.
Air Clean ON signal is received
• OFF condition:
IFAN is OFF
Air Clean OFF signal is received
12A.16. E.S.F – Electro Static Filter
12Α.16.1. E.S.F output logic
• Models: All
• Operation mode: All
• E.S.F is ON when all the following condition are satisfied:
a. IFAN turn ON.
b. Air Clean ON signal is received.
c. Safe switch is pressed
• E.S.F is OFF only if one of the following condition isn’t satisfied :
a. IFAN is OFF
b. Air Clean OFF signal is received
c. Safe switch is loosed.
Note: That output logic will be active only if the E.S.F. Enable bit is 1 in the R/C
message (default = 1) as described in Appendix A.