CONTROL SYSTEM
Revision 0
12A.14. Clogged Air filter
Filter LED ON after 512 HR
Filter LED is turned OFF, and the Filter Timer is restarted by pressing the reset
button.
12A.15. Ionizer
Ionizer output logic
Models: All
Operation mode: All
ON condition:
IFAN turn ON.
Air Clean ON signal is received
OFF condition:
IFAN is OFF
Air Clean OFF signal is received
12A.16. E.S.F – Electro Static Filter
12Α.16.1. E.S.F output logic
Models: All
Operation mode: All
E.S.F is ON when all the following condition are satisfied:
a. IFAN turn ON.
b. Air Clean ON signal is received.
c. Safe switch is pressed
E.S.F is OFF only if one of the following condition isn’t satisfied :
a. IFAN is OFF
b. Air Clean OFF signal is received
c. Safe switch is loosed.
Note: That output logic will be active only if the E.S.F. Enable bit is 1 in the R/C
message (default = 1) as described in Appendix A.