Engineering Data Manual
EDM HAN-A.1GB
Date : October 2008
Supersedes : None
uRooftop Air Conditioners - Heat Pump Version
HAN 10 to 31

Other manuals for Airwell HAN 10

Questions and Answers

  • T
    Tiffany GallegosAug 20, 2025
    Why is the evaporator freezing in my Airwell HAN 10 Air Conditioner?
    • D
      Dale GriffinAug 20, 2025
      If the evaporator is freezing in your Airwell Air Conditioner, it could be due to clogged filters. Try replacing the filters. Another possible cause is an insufficient refrigerant charge, in which case you should add refrigerant charge.
  • V
    Vanessa CarrilloAug 22, 2025
    How to fix excessive noise in my Airwell Air Conditioner?
    • P
      Phyllis CisnerosAug 22, 2025
      Excessive noise in your Airwell Air Conditioner can stem from several sources. Vibrating pipe work may be the cause, so ensure the pipe work is correctly attached. A whistling noise from the thermostatic expansion valve indicates you may need to add refrigerant charge. A noisy compressor could mean you need to check the pressure difference of the 4-ways valves. If there is no pressure increase or mechanical damage to the compressor, contact an approved Service Centre.
  • T
    tloveAug 25, 2025
    What causes the low pressure pressostat to activate in my Airwell Air Conditioner?
    • J
      Jennifer RiveraAug 26, 2025
      If the low pressure pressostat is being activated in your Airwell Air Conditioner, it may be due to a leak. Identify and repair the leak. Another reason could be insufficient refrigerant fluid charge, so add refrigerant charge. A further cause might be low air volume on the evaporator, so check the blower and duct.
  • E
    Elizabeth ChangAug 27, 2025
    Why does my Airwell Air Conditioner operate continuously but without performing?
    • G
      Gerald BarronAug 27, 2025
      If your Airwell Air Conditioner unit runs continuously but isn't performing, it could be due to an insufficient refrigerant charge. In this case, top up the refrigerant fluid charge. Alternatively, there may be reduced output. Check the 4 way valve on the compressor and replace the valve if necessary.
  • J
    Jerry WarnerAug 30, 2025
    What to do if Airwell Air Conditioner has reduced output in both Heating and Cooling mode?
    • S
      Stacey WilkersonAug 30, 2025
      If your Airwell Air Conditioner has reduced output in both heating and cooling modes, it could be due to a compressor operating fault, in which case you should contact an approved Service Centre. Another cause could be a dirty outdoor coil, so try cleaning the coil. Also, insufficient refrigerant charge could be the problem, so add refrigerant charge. Finally, a lack of air flow could be the cause, so clean the battery, replace the filter and check the air flow/pressure settings.
  • S
    Stephanie RojasSep 1, 2025
    Why is the high pressure pressostat being activated in my Airwell Air Conditioner?
    • S
      Samuel NelsonSep 1, 2025
      If the high pressure pressostat is being activated in your Airwell Air Conditioner, it could be due to several reasons. First, check the operation of the high pressure pressostat and replace it if required, as it may be operating incorrectly. Another cause might be an outlet valve that is partially closed, so open the valve and replace it if required. Non-condensable particles in the circuit could also be the problem, so bleed the circuit. Finally, the condenser fan may not be operating, so check the wiring and the motors, and repair or replace them if required.
  • J
    jdiazSep 4, 2025
    Why is the suction line frozen on my Airwell HAN 10?
    • K
      kimberly38Sep 4, 2025
      If you notice a frozen suction line on your Airwell Air Conditioner, it might be because the overheating setting on the thermostatic expansion valve is too low. Try increasing the setting. Another possible cause is an insufficient refrigerant charge, so add refrigerant charge.
  • M
    Miranda PerezSep 6, 2025
    What causes a low oil level in the compressor of my Airwell HAN 10 Air Conditioner?
    • J
      Janice FoxSep 6, 2025
      A low oil level in the compressor of your Airwell Air Conditioner can be due to a few reasons. It could be caused by one or several oil or gas leaks in the circuit, so locate and repair the leaks and add oil. It may also be due to mechanical compressor damage, in which case you should contact an approved Service Centre. Finally, it could be a crankcase oil heater resistance fault, so check the electrical circuit and the condition of the resistance, and replace defective parts if necessary.
  • A
    Anna GentrySep 9, 2025
    Why is the liquid line too hot on my Airwell HAN 10 Air Conditioner?
    • J
      jennifersmithSep 9, 2025
      If the liquid line is too hot in your Airwell Air Conditioner, it is likely due to an insufficient refrigerant charge. Locate and eliminate the causes of charge losses and top up the refrigerant fluid charge.
  • J
    johnsonjesseSep 12, 2025
    What to do if the fans do not operate on my Airwell HAN 10 Air Conditioner?
    • H
      Heather EstesSep 12, 2025
      If the fans in your Airwell Air Conditioner are not working, it could be due to electrical circuit problems, so check the connections. Alternatively, the internal circuit thermal cut-out may be activated, in which case you should contact an approved Service Centre.

Airwell HAN 10 Specifications