Electrical Control Function
82 Electrical Control System
3.5
3.0
High
Low
1.0
Medium
1.5
For DKH,HND, Console
a
b
c
d
5.0
4.0
2.5
1.0
6.0
T1-24
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
1.3.2 Cooling Mode
1.3.2.1 Compressor running rules
The compressor will run at corresponding frequency according to the gross amendatory capacity demand.
Amendatory capacity demand.
Meanwhile the maximum running frequency will be adjusted according to the outdoor ambient temp.
43
41
38
T4LimFre1_ADD
No limit
T4LimFre2_ADD
T4LimFre3_ADD
42
39
37
49
46
T4LimFre4_ADD
T4LimFre5_ADD
48
45
1.3.2.2 Outdoor fan running rules