EasyManuals Logo

Airwell YCV Series Installation Manual

Airwell YCV Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
8
Unit pipe spec and connection method (unit: mm)
A. Outdoor unit
Model
15.88
19.05
Flared joint
9.52
9.52
Flared joint
Gas pipe side Liquid pipe side
Diameter Connecting method Diameter Connecting method
YCV080
YCV180
B. Indoor unit
Gas pipe side
Model
Capacity
12.7
15.88
Flared joint
Liquid pipe side
Diameter
Connecting method
Diameter
Connecting method
24
18
16
12
09
Flared joint
9.52
12.7
12.7
6.35
9.52
6.35
6.35
6.35
C. Pipe spec and the torque
Not less than 28.58
diameter Thickness(mm)
0.8
0.8
1.0
1.0
1.0
1.2
Torque(N.m)
16~20
40~50
90~120
100~140
——
6.35
9.52
12.7
15.88
19.05
25.4
More than 1.4
1.1
22.22
Note: If the copper pipe with outer diameter 19.05 is coil pipe, the thickness should be over 1.1.
——
——
19.05 9.52
B-YCV150