3
If the connected units quantity and the total capacity is in the allowable range?
If the refrigerant pipe length is in the limited range?
If the pipe size is proper? And if the pipe is installed horizontally?
If the branch pipe is installed horinzontally or vertically?
If the additional refrigerant is counted correctly and weighed by the standard balance?
If there is refrigerant leakage?
If all the indoor power supplies can be on/off simultaneously?
If the power voltage is in compliance with the data marked on the rating label?
If the address of indoors has been set?
indoor
capacity (100W)
outdoor
combination type indoor Qty total indoor capacity (100W)
80
180
single
single
5
9
40-104
90-234
indoor capacity (100W)
22
28
36
40
45
56
71
TAU335
total indoor capacity (100W)
less than 335
branch pipe
(optional)
Notice:
Total capacities of indoor units being used ≤ 100% of rated capacities of outdoor unit
150
single
8 75-195
Installation instruction
In installation, please check specially the below items:
(1) Before installation
1) Before installation, check if the model, power supply, pipe, wires and parts purchased
respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.