21
Failure code
Digital tube
indication
on master
unit
Indication
on wired
controller
(hex)
Failure code
denition
Failure description Remarks
115 115
Voltage too high
of DC bus line of
transducer
Voltage of power source is too high
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
116 116
Communication
abnormal between
transducer and
control PCB
Communication is disconnected Resumable
117 117
Transducer over
current (software)
Compressor startup fails for 5 times continuously, or
compressor is running down till stops caused by over
current or over heat
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
118 118
Compressor
startup failure
The sensor used for current detecting of transducer is
abnormal, disconnected or incorrectly connection
119 119
Detecting circuit of
transducer current
is abnormal
Current detection sensor of frequency controller is abnormal
or unconnected or connected wrongly.
120 120
Power supply
of transducer
abnormal
Power supply of transducer is broken down instantly
121 121
Power supply of
inverter board is
abnormal
Power supply of inverter board is broken down instantly
3 times in an
hour, conrm
failure; once
conrmation,
un-resumable
122 122
Radiator temp.
sensor of
transducer
abnormal
Resistor of temp.sensor abnormal or temp.sensor
disconnected
123 123
Transient over
current in IPM
module rectier
side hardware
Transient over current in IPM module rectier side hard
ware
When there is no failure, if the starting condition can not be met, digital tube on master unit will display stand-by code:
555 Standby state of capacity overmatch
When capacity is over 130% or lower than
50%, the system is standby.
Resumable555.1 Outdoor ambient temperature too high (heating) Ta>27°C, Standby
555.3
Outdoor ambient temperature too high or too low
(cooling)
Ta>54°C or Ta<-10°C, Standby

Other manuals for Airwell YCV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airwell YCV Series and is the answer not in the manual?

Airwell YCV Series Specifications

General IconGeneral
BrandAirwell
ModelYCV Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals