10
EN
On/Off. Pressing the icon turns the zone in which the thermostat is located on or off.
HVAC control
23° Set-point temperature. Select the set-point temperature using the control bar (by pressing
or sliding). You can select the desired set-point temperature in steps of 0.5°C. Slide to set the
temperature with a larger range.
The temperature range permitted in heating mode is: 15-30°C. In cooling mode: 18-30°C. These
vary depending on the level of efficiency (Eco-Adapt) that has been selected on the master
interface.
Stop. The HVAC system remains shut down regardless of the status of the rest of the zones.
In addition, all terminal elements (grilles, dampers, etc.) will be closed.
Cooling. In this operation mode, the system only operates with the AC unit in cooling mode
when any of the zones associated to the system is generating demand (set-point temp. < room
temp.).
Heating. In this operation mode, the system only operates with the AC unit in heating mode
when any of the zones associated to the system is generating demand (set-point temp. > room
temp.).
Ventilation. In this operation mode, the system only operates with the AC unit in ventilation
mode when any of the zones associated to the system is generating demand (set-point temp. <
room temp.).
This indicates the mode in which the system is working. If your Airzone Think thermostat is
a master thermostat, access the settings menu to change the operation mode. The available
modes are as follows:
Operation mode
Dry*. In this operation mode, the system only operates with the AC unit in dry mode,
refreshing the environment and prioritizing the operation to reduce humidity, when any of the
zones is generating demand (set-point temp. < room temp.).
*Note: This mode is ideal for days when humidity is high: it reduces the occurrence of water
particles on the grilles.
If your Airzone Think thermostat is a master thermostat, access the settings menu to change
the fan speed. The default setting is Automatic mode, imposing airflow based on the number
of zones on demand. Depending on the type of installation, it will be possible to select the
speed manually from the master thermostat.
Fan speed
High speed Low speed
Medium speed Automatic speed

Table of Contents

Other manuals for Airzone FLEXA 3.0 IBPRO6