EasyManua.ls Logo

Algodue ELETTRONICA UPM307 - Utility Setup Options: Contrast, Clear, Language; LCD Contrast Adjustment; Clearing Counters and Peak Values; Backlight and Language Settings

Algodue ELETTRONICA UPM307
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-2
ENGLISH
Exception codes
MODBUS protocol manual
MODBUS TCP
Values contained in Response messages are in hexa format.
Response example in case of MODBUS TCP: 010000000003018302
Example Byte Description No. of bytes
01 - Transaction identifier 1
00 High
Protocol identifier 4
00 Low
00 High
00 Low
03 - No. of byte of next data in this string 1
01 - Unit identifier 1
83 - Function code (80+03) 1
02 - Exception code 1
Exception codes for MODBUS TCP are following described:
01 ILLEGAL FUNCTION: the function code is unknown by the server.
02 ILLEGAL DATA ADDRESS: the data address received in the query is not an allowable
address for the instrument (i.e. the combination of register and transfer length is
invalid).
03 ILLEGAL DATA VALUE: a value contained in the query data field is not an allowable value
for the instrument.
04 SERVER FAILURE: the server failed during the execution.
05 ACKNOWLEDGE: the server accepted the server invocation but the service requires a
relatively long time to execute. The server therefore returns only an aknowledgement
of the service invocation receipt.
06 SERVER BUSY: the server was unable to accept the MB request PDU. The client application
has the responsability of deciding if and when re-sending the request.
0A GATEWAY PATH UNAVAILABLE: the ETHERNET interface is not configured or cannot
communicate.
0B GATEWAY TARGET DEVICE FAILED TO RESPOND: the instrument is not available in the
network.

Other manuals for Algodue ELETTRONICA UPM307