EasyManua.ls Logo

Allen-Bradley 1398 ULTRA Plus Series - Page 32

Allen-Bradley 1398 ULTRA Plus Series
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1398-5.1 — January 2000
2-14 Install the ULTRA Plus PDM Components
1398-PDM-25, 50, 100, and 150 Power Supply Module
7KHSRZHUVXSSO\PRGXOHVKRXOGEHFHQWUDOO\ORFDWHGWRPLQLPL]HWKHGLVWDQFH
EHWZHHQLWDQGWKH3'0PRGXOHV7KHKLJKHUFXUUHQWUDWLQJ3'0PRGXOHV
VKRXOGEHORFDWHGFORVHVWWRWKHSRZHUVXSSO\PRGXOH
PSM Auxiliary Transformers
)LJXUHVKRZVWKHPRXQWLQJGLDJUDPDQGFRQQHFWLRQVIRUWKH360
$X[LOLDU\7UDQVIRUPHU
Figure 2.9
PSM Auxiliary Transformer mounting
9101-0233
1.
5.00 MAX
4.38
5.50 MAX.
4.256.25
1.
8.0 MIN. CLEARANCE RECOMMENDED FOR ACCESS TO WIRING
RING OR SPADE LUG CONNECTORS (NOT PROVIDED) ARE REQUIRED
FOR WIRING CONNECTIONS TO THE TRANSFORMER.
INPUT (PRIMARY) CONNECTIONS: H1,H4
480 VAC INPUT: JUMPER H3 to H2
240 VAC INPUT: JUMPER H1 to H3 AND H2 to H4
OUTPUT (SECONDARY) CONNECTIONS: X1,X2
120 VAC
H1 H3 H2 H4
X1X2
OUTPUT POWER @ 50/60Hz
110 VAC OUTPUT VOLTAGE
50˚C MAX. TEMPERATURE RISE
500 VA MIN.
NOMINAL OPERATING VOLTAGES 480 OR 240 INPUT, 120 OUTPUT
460 OR 230 INPUT, 115 OUTPUT
440 OR 220 INPUT, 110 OUTPUT
CONNECTION INSTRUCTIONS
X2 X1
H1 H2H3 H4
MAX.
0.69
0.31
8-32 TERMINAL SCREWS (6)
NOTES:
SCHEMATIC SYMBOL
SPECIFICATIONS: