10 Remote I/O Scanner
Publication 1747-IN060B-EN-P - June 2001
For Series A Scanner Retrofits
Refer to the illustration on page 9. To eliminate the need to strip the cable back,
follow these steps:
1. Attach the shield wire and a short piece of #20 AWG wire (dotted line) to the
shield lug of the RIO link connector.
2. Attach the other end of the #20 AWG wire to the ring terminal lug.
3. Attach the ring terminal lug to a chassis mounting bracket.
Specifications
IMPORTANT
The RIO cable shield must be grounded at the scanner end only.
Ensure that the unshielded portion of the link communication
wire (blue and clear) is as short as possible.
Backplane Current Consumption 600 mA at 5V dc
Operating Temperature 0°C to +60°C (+32°F to +140°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 5 to 95% without condensation
Noise Immunity NEMA Standard ICS 2-230
Agency Certification UL listed / CSA Certified
Class I, Division 2, Groups A,B, C, D
CE marked for all applicable directives