30 Rockwell Automation Publication 1769-IN028I-EN-P - July 2020
Compact I/O Expansion Power Supplies
Environmental Specifications
Attribute
1769-PA2,
1769-PA2K
(1)
1769-PB2,
1769-PB2K
1769-PA4,
1769-PA4K
1769-PB4,
1769-PB4K
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold
IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0 °C < Ta < 60 °C (32 °F < Ta < 140 °F)
Temp er atu re,
non-operating
IEC 60068-2-1 (Test Ab, Unpackaged
Non-operating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged
Non-operating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged
Thermal Shock)
-40 < Ta < +85 °C (-40 < Ta < +185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
DIN rail mount: 20 g
Panel mount: 30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
DIN rail mount: 30 g
Panel mount: 40 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC61000-4-2
6 kV contact
8 kV air discharges
Radiated RF immunity
IEC61000-4-3
10V/m with 1 kHz
sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 1890 MHz
10V/m with 1 kHz
sine-wave 80% AM
from 2000…2700
MHz
10V/m with 1 kHz
sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 1890 MHz
10V/m with 1 kHz
sine-wave 80% AM
from 2000…2700
MHz
10V/m with 1 kHz
sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz
50% Pulse 100% AM
at 1890 MHz
10V/m with 1 kHz
sine-wave 80% AM
from 2000…2700
MHz
10V/m with 1 kHz sine-
wave 80%AM from
80…2000 MHz
10V/m with 200 Hz 50%
Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50%
Pulse 100% AM at 1890
MHz
10V/m with 1 kHz sine-
wave 80% AM from
2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±2 kV at 5 kHz on AC
power ports
±2 kV at 5 kHz on
24V DC PWR OUT
ports
±2 kV at 5 kHz on DC
power ports
±2 kV at 5 kHz on AC
power ports
±2 kV at 5 kHz on DC power
ports