Publication17855.13 April 1996
Enhanced PLC5
Programmable Controller
Firmware Upgrade
(Catalog Numbers 1785-L11B, -L20B, -L30B,
-L40B, -L40L, -L60B, -L60L, -L80B)
These instructions describe:
an important safety precaution involving static electricity
discharges
how to upgrade the processor firmware
For more information about PLC-5 processors, see the Enhanced and
Ethernet PLC-5 User Manual, publication number 1786-6.5.12. For
more information, contact your Allen-Bradley service representative.
Printed circuit board components and Programmable Read-only
Memory (PROM) devices can be damaged during routine handling
and installation. Follow these precautions to reduce static electricity
discharges before you upgrade the processor firmware.
Handle the printed circuit boards and PROMs by the case or
carrier without touching the pins or the edge connector.
Use a static-free workstation.
Connect the static-free workstation to ground through a minimum
200K ohm resistance.
Wear a grounded, conductive wrist strap with a minimum 200K
ohm resistance.
Ground all tools before you begin to upgrade the firmware.
Control the relative humidity of the installation area – ideal
conditions are 40% to 60% relative humidity.
AB
Installation Instructions
Using These Instructions
Before You Install ...
Allen-Bradley Replacements

Other manuals for Allen-Bradley 1785-L11B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1785-L11B and is the answer not in the manual?

Allen-Bradley 1785-L11B Specifications

General IconGeneral
BrandAllen-Bradley
Model1785-L11B
CategoryController
LanguageEnglish

Related product manuals